Power Factor Improvement Capacitor Bank PFC

  • H
  • Products
  • Reactive Power Compensator (SVC)
  • Power Factor Improvement Capacitor Bank PFC

summary

The power factor improvement capacitor bank is the most economic and effective method for improving the power factor of power system. By improving the power factor of system with a capacitor bank, it is possible to reduce loss, compensate voltage drop, increase an allowance rate of transformer, and therefore improve the power quality of system.

Product Features

Two types of capacitor bank are designed and manufactured depending on a protection type (capacity failure detection type). The capacitor bank type and applicable voltage range according to a protection type are presented in the following table

Product Features
Protection type Detection factor Bank type (application voltage)
Open delta Zero phase voltage detection Frame (up to 36kV) / Panel (up to 36kV)
Voltage difference(DEVI) Detection of differential voltage between two parallel groups Frame (up to 36kV) / Panel (up to 36kV)

Product Principles

CAPACITOR BANK ENGINEERING

Installation Effects

By supplying the capacitor bank to leading reactive current of capacitor, it is possible to reduce the inductive reactive current used in loads and therefore lower the burden of power generator. Aside from that, the capacitor bank for power factor improvement has the following advantages

    • System power factor improvement
    • Voltage drop compensation
    • Reduction in line and transformer loss
    • Increase in an allowance rate of transformer
    • Power rate reduction

Product Specification

Open delta protection type

Product Specification
Circuit voltage Frequency[Hz] Rated capacity[kvar] Composition Series reactor L=6%
22.9 60 500 83.4kvar × 3units 30kvar
1000 167kvar × 6units 60kvar
1500 250kvar × 6units 90kvar
2000 167kvar × 12units 120kvar
2500 209kvar × 12units 150kvar

Voltage difference protection type

Product Specification
Circuit voltage Frequency[Hz] Rated capacity[kvar] Composition Series reactor L=6%
22.9 60 500 83.4kvar × 6units 30kvar
1000 167kvar × 6units 60kvar
1500 250kvar × 6units 90kvar
2000 167kvar × 6units 120kvar
2500 209kvar × 6units 150kvar
3000 250kvar × 6units 180kvar
4000 167kvar × 6units 240kvar
5000 278kvar × 6units 300kvar

Design Drawings

  • Open delta Protection type

  • Voltage difference Protection type